BRONZE BALANCING VALVE

Model: #B01

Specification

According to the GB/T 28636-2012 standard ,When
the valve’ s opening rate is greater than 50%, the
deviation is lower than ± 5%. Based on this, it is
suggested to choose a valve with at least 50%
opening rate when working under the design flow.
Additionally, in order to ensure adequate on-site
commissioning allowance, it is recommended to set
the valve at around 75% opening rate.

Product Detail

Application

The Series UTD-B01 Static Balancing Valve is designed for flow
balancing in cooling, heating or process water systems. Its
shutoff feature can be instead the Globe valve. It also has
the function of locking of maximum range. The function of
locking will be opened after its system debugged. If the prod-
ucts need to be repaired, you can close the Static Balancing
Valve, and then directly return to the maximum
range. It can avoid the second text, save many time and
cost. Its measuring joint enable convenient system trouble-
shooting. Static balancing valve be used in water supply or
return water pipe.

Features

Accurate flow control
Numerical indicator of opening rate on the hand wheel
open lacking is easy
Shut-off function achieved by hand wheel
Self-sealing measuring points to protect against leakage

Technical Specification

Dimensions: DN15-DN50
Working Temperature: -10 to 120°C
Working Pressure: PN25
Fluid Medium: Cold and Hot Water / Ethylene Glycol
Connection: Threaded Connection
Connection Standard: EN10226 GB/T 7306.1-2000

Materials

Valve Body: Brass/ Bronze
Valve Core: Brass/ Bronze
Valve Base Sealing: PTFE
Valve Bonnet: Brass/ Bronze
Valve Stem: Brass/ Bronze
Core Rod: DZR Brass CW602N
Hand Wheel: Plastic ABS
Sealling: EPDM
Measuring Points: Brass